Skip to main content

ENERGY_EFFICIENCY_IN_ELECTRICAL_UTILITIES (Chapter 3:Compressed Air System)


ENERGY_EFFICIENCY_IN_ELECTRICAL_UTILITIES   

(Chapter 3:Compressed Air  System)

Introduction 

Air compressors account for significant amount of electricity used in Indian industries. Air compressors are used in a variety of industries to supply process requirements, to operate pneumatic tools and equipment, and to meet instrumentation needs. Only 10-30% of energy reaches the point of end-use (Figure 3.1), and balance 70-90% of energy of the power of the prime mover being converted to unusable heat energy and to a lesser extent lost in form of friction, misuse and noise. 

Compressor Types
Compressors are broadly classified as: Positive displacement compressor and Dynamic compressor (Figure 3.2). 
Positive displacement compressors increase the pressure of the gas by reducing the volume. Positive displacement compressors are further classified as reciprocating and rotary compressors.

Dynamic compressors increase the air velocity, which is then converted to increased pressure at the outlet. Dynamic compressors are basically centrifugal compressors and are further classified as radial and axial flow types. 

The flow and pressure requirements of a given application determine the suitability of a particulars type of compressor.    

Positive Displacement Compressors 
Reciprocating Compressors 
Reciprocating compressors (Figure 3.3) are the most widely used type for air compression. They are characterized by a flow output that remains nearly constant over a range of discharge pressures. Also, the compressor capacity is directly proportional to the speed. The output, however, is a pulsating one. 
Reciprocating compressors are available in many configurations, the four most widely used of which are horizontal, vertical, horizontal balance-opposed and tandem. Vertical type reciprocating compressors are used in the capacity range of 50 — 150 cfm. Horizontal balance opposed compressors are used in the capacity range of 200 — 5000 cfm in multi-stage design and up to 10,000 cfm in single stage designs. 
Reciprocating compressors are also available in variety of types: 
¢ Lubricated and non-lubricated 
¢ Single or multiple cylinder
¢ Water or air-cooled
¢ Single or multi stage 

In the case of lubricated machines, oil has to be separated from the discharge air. Non-lubricated compressors are especially useful for providing air for instrumentation and for processes which require oil free discharge. However non-lubricated machines have higher specific power consumption (kW/ cfm) as compared to lubricated types.
Single cylinder machines are generally air-cooled, while multi-cylinder machines are generally water cooled, although multi-stage air-cooled types are available for machines up to 100 kW. Water-cooled systems are more energy efficient than air-cooled systems. 
Two stage machines are used for high pressures and are characterized by lower discharge temperature (140 to 160°C) compared to single-stage machines (205 to 240°C). In some cases, multi-stage machines may have a lower specific power consumption compared to single stage machines operating over the same total pressure differential. Multi-stage machines generally have higher investment costs, particularly for applications with high discharge pressure (above 7 bar) and low capacities (less than 25 cfm). Multi staging has other benefits, such as reduced pressure differential across cylinders, which reduces the load and stress on compressor components such as valves and piston rings. 

Rotary Compressors 
Rotary compressors (Figure 3.4) have rotors in place of pistons and give a continuous, pulsation free discharge air. They are directly coupled to the prime mover and require lower starting torque as compared to reciprocating machine. They operate at high speed and generally provide higher throughput than reciprocating compressors. Also they require smaller foundations, vibrate less, and have a lower number of parts - which means less failure rate. 
Among rotary compressor, the Roots blower (also called as lobe compressor) and screw compressors are among the most widely used. The roots blower is essentially a low-pressure blower and is limited to a discharge pressure of | bar in single-stage design and up to 2.2 bar in two stage design. 
The most common rotary air compressor is the single stage helical { or spiral lube oil flooded screw air compressor. These compressors consist of two rotors, within a casing where the rotors compress the air internally. There are no valves. These units are basically oil cooled   

(with air cooled or water cooled oil coolers) where the oil seals the internal clearances. Since the cooling takes place right inside the compressor, the working parts never experience extreme operating temperatures. The oil has to be separated from discharge air. Because of the simple design and few wearing parts, rotary screw air compressors are easy to maintain, to operate and install.
The oil free rotary screw air compressor uses specially designed air ends to compress air without oil in the compression chamber producing true oil free air. These compressors are available as air-cooled or water cooled types and provide the same flexibility as oil flooded rotary compressors. 
There is a wide range of availability in configuration and in pressure and capacity. Dry types deliver oil-free air and are available in sizes up to 20,000 cfm and pressure upto 15 bar. Lubricated types are available in sizes ranging from 100 to 1000 cfm, with discharge pressure up to 10 bar.   
  
Dynamic Compressors 
Dynamic compressors (Figure 3.5) are mainly centrifugal compressors and operate on similar principles to centrifugal pump. These compressors have appreciably different characteristics as compared to reciprocating machines. A small change in compression ratio produces a marked change in compressor output and efficiency. Centrifugal machines are better suited for applications requiring very high capacities, typically above 12,000 cfm. 
The centrifugal air compressor is an oil free compressor by design. The oil-lubricated running gear is separated from the air by shaft seals and atmospheric vents. The centrifugal is a continuous duty compresor,with few moving parts, and is particulary suited to high volume applications, especially where oil free air is required.  

A single-stage centrifugal machine can provide the same capacity as a multi-stage reciprocating compressor. Machines with either axial or radial flow impellers are available. 

The major limitation of a centrifugal compressor is that it operates at peak efficiency at design point only and any deviation from the operating point penalizes efficiency. When selecting centrifugal compressors, close attention should be paid during system design to ensure that at high pressure, with the consequent reduction in flow, the surge point or zone of unstable operation is not reached.

Axial flow compressors are suitable for higher compression ratios and are generally more efficient than radial compressors. Air is allowed to pass through series of alternate rows of rotating blades (attached with rotors) and fixed blades (fixed to casing), having direction of flow parallel to the axis. 

The general selection criteria for compressor is given in the Table 3.1 

Comparison of Different Compressors 
The power consumption of various compressors depends on the operating pressure, free air delivery and efficiency etc. The variations in power consumption during unloading/part load operation are more significant and depend on the type of compressor and method of capacity control. The relative efficiencies and part load power consumption of different compressors are given in Table 3.2. 
In case of reciprocating machines, the unload power consumption is in the order of 25% of full load power. While in screw compressors, the unload power consumption is marginally higher compared to reciprocating machines.
It is preferable to use screw compressors for constant air requirement. If screw compressors have to be installed for fluctuating loads, it is desirable to have screw compressor with variable speed drive to further optimize unload power consumption.
Some of the plants have adopted the strategy of operating screw compressor at full load for meeting the base-load requirement and reciprocating compressor for fluctuating load to optimize on unload power consumption.  

Compressor Performance 
Capacity of a Compressor: Free Air Delivery (FAD) 
Free air, as defined by CAGI (Compressed Air & Gas Institute) is air at ATMOSPHERIC conditions at any specific location. Because the barometer and temperature may vary at different localities and at different times, it follows that this term does not mean air under standard conditions. 
Measured in CFM (Cubic feet per minute) this is the amount of compressed air converted back to the actual inlet (free air) conditions before it was compressed. In other words, the volume of air, which is drawn in from the atmosphere by the compressor, then compressed and delivered at a specific pressure. 

Compressor Efficiency Definitions
Several different measures of compressor efficiency are commonly used: volumetric efficiency, adiabatic efficiency, isothermal efficiency and mechanical efficiency. 
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power divided by the actual power consumption. The figure obtained indicates the overall efficiency of compressor and drive motor. 

Isothermal Efficiency 
The calculation of isothermal power does not include power needed to overcome friction and generally gives an efficiency that is lower than adiabatic efficiency. The reported value of efficiency is normally the isothermal efficiency. This is an important consideration when selecting compressors based on reported values of efficiency.

Volumetric Efficiency  
For practical purposes, the most effective guide in comparing compressor efficiencies is the specific power consumption 1.e. kW/volume flow rate, for different compressors that would provide identical duty. 

Compressed Air System Components 
Compressed air system consist of following major components: Intake air filters, inter-stage coolers, after coolers, air dryers, moisture drain traps, receivers, piping network, filters, regulators and lubricators (see Figure 3.6). 

Intake Air Filters: Prevent dust from entering compressor; Dust causes sticking valves, scoured cylinders, excessive wear etc. 
Inter-stage Coolers: Reduce the temperature of the air before it enters the next stage to reduce the work of compression and increase efficiency. They are normally water-cooled. 
After Coolers: The objective is to remove the moisture in the air by reducing the temperature in a water-cooled heat exchanger.
Air-dryers: The remaining traces of moisture after after-cooler are removed using air dryers because air for instrument and pneumatic equipment has to be relatively free of any moisture. The moisture is removed by using adsorbents like silica gel /activated carbon or refrigerant dryers. 
Moisture Drain Traps: Moisture drain traps are used for removal of condensate from the compressed air. These traps resemble steam traps and various types used are manual drain cocks, timer based / automatic drain valves etc. 
Receivers: Air receivers are provided as storage and smoothening pulsating air output - reducing pressure variations from the compressor.
Efficient Operation of Compressed Air Systems 
Location of Compressors 
The location of air compressors and the quality of air drawn by the compressors will have a significant influence on the amount of energy consumed. Compressor performance as a breathing machine improves with cool, clean, dry air at intake. 

Cool air intake 
As a thumb rule, “Every 4°C drop in inlet air temperature results in lower energy consumption by 1 % to achieve equivalent output”. Hence, cool air intake leads to a more efficient compression (see Table 3.3). Table 3.3 
Since heat is generated during operation of compressors, temperature of air inside the compressor room will be higher than the ambient temperature. Hence, it is preferable to draw cool ambient air from outside. While extending air intake from the outside of room, care should be taken to minimize excess pressure drop in the suction line, by selecting a large diameter duct with minimum number of bends.

Dust Free Air Intake 
Dust in the suction air causes excessive wear of moving parts and results in malfunctioning of the valves due to abrasion. Suitable air filters should be provided at the suction side. 
Air filters should have high dust separation capacity, low-pressure drops and robust design to avoid frequent cleaning and replacement. See Table 3.4 for effect of pressure drop across air filter on power consumption. Air filters should be selected based on the compressor type and installed as close to the compressor as possible. As a thumb rule “For every 250 mm WC pressure drop increase across at the suction path due to choked filters etc, the compressor power consumption increases by about 2 percent for the same output” 
Hence, it is advisable to clean inlet air filters at regular intervals to minimize pressure drops. Manometers or differential pressure gauges across filters may be provided for monitoring pressure drops so as to plan filter-cleaning schedules.  

Dry Air Intake 
Atmospheric air always contains some amount of water vapour, depending on the relative humidity, being high in wet weather. The moisture level will also be high if air is drawn from a damp area - for example locating compressor close to cooling tower, or dryer exhaust is to be avoided (see Table 3.5).  


The moisture-carrying capacity of air increases with a rise in temperature and decreases with increase in pressure. 

Elevation 
The altitude of a place has a direct impact on the volumetric efficiency of the compressor. The effect of altitude on volumetric efficiency is given in the Table 3.6. It is evident that compressors located at higher altitudes consume more power to achieve a particular delivery pressure than those at sea level, as the compression ratio is higher.  

Cooling Water Circuit
Most of the industrial compressors are water-cooled, wherein the heat of compression is removed by circulating cold water to cylinder heads, inter-coolers and after-coolers. The resulting warm water is cooled in a cooling tower and circulated back to compressors. The compressed air system performance depends upon the effectiveness of inter-coolers, after coolers, which in turn are dependent on cooling water flow and temperature. 
 Further, inadequate cooling water treatment can lead to increase, for example, in total dissolved solids (TDS), which in turn can lead to scale formation in heat exchangers. The scales, not only act as insulators reducing the heat transfer, but also increase the pressure drop in the cooling water pumping system.
Use of treated water or purging a portion of cooling water (blow down) periodically can maintain TDS levels within acceptable limits. It is better to maintain the water pH by addition of chemicals, and avoid microbial growth by addition of fungicides and algaecides.

Efficacy of Inter and After Coolers 
Efficacy is an indicator of heat exchange performance- how well intercoolers and after coolers are performing. Inter-coolers are provided between successive stages of a multi-stage compressor to reduce the work of compression (power requirements) - by reducing the specific volume through cooling the air - apart from moisture separation.  
Ideally, the temperature of the inlet air at each stage of a multi-stage machine should be the same as it was at the first stage. This is referred to as “perfect cooling” or isothermal compression. The cooling may be imperfect due to reasons described in earlier sections. Hence in actual practice, the inlet air temperatures at subsequent stages are higher than the normal levels resulting in higher power consumption, as a larger volume is handled for the same duty (See Table 3.7). 
It can be seen from the Table 3.7 that an increase of 5.5°C in the inlet air temperature to the second stage results in a 2 % increase in the specific energy consumption. Use of water at lower temperature reduces specific power consumption. However, very low cooling water temperature could result in condensation of moisture in the air, which if not removed would lead to cylinder damage. 
Similarly, inadequate cooling in after-coolers (due to fouling, scaling etc.), allow warm, humid air into the receiver, which causes more condensation in air receivers and distribution lines, which in consequence, leads to increased corrosion, pressure drops and leakages in piping and end-use equipment. Periodic cleaning and ensuring adequate flow at proper temperature of both inter coolers and after coolers are therefore necessary for sustaining desired performance. Typical cooling water requirement is given in Table 3.8.  
Pressure Settings Compressor operates between pressure ranges called as loading (cut-in) and unloading (cut-out) pressures. For example, a compressor operating between pressure setting of 6 - 7 kg/cm? means that the compressor unloads at 7 kg/cm? and loads at 6 kg/cm’. Loading and unloading is done using a pressure switch. 
For the same capacity, a compressor consumes more power at higher pressures. They should not be operated above their optimum operating pressures as this not only wastes energy, but also leads to excessive wear, leading to further energy wastage. The volumetric efficiency of a compressor is also less at higher delivery pressures.

Reducing Delivery Pressure:
The possibility of lowering (optimising) the delivery pressure settings should be explored by careful study of pressure requirements of various equipments, and the pressure drop in the line between the compressed air generation and utilization points. Typical power savings through pressure reduction is shown in Table 3.9.   
The pressure switches must be adjusted such that the compressor cuts-in and cuts-out at optimum levels.

A reduction in the delivery pressure by | bar in a compressor would reduce the power consumption by 6— 10%. For example, reduction of delivery pressure by | kg/cm? (from 8 kg/cm? to 7 kg/cm?) would result in 9% input power savings. 

Compressor modulation by Optimum Pressure Settings: 
Very often in an industry, different types, capacities and makes of compressors are connected to a common distribution network. In such situations, proper selection of a right combination of compressors and optimal modulation of different compressors can conserve energy.  
When more than one compressor feeds a common header, compressors have to be operated in such a way that the cost of compressed air generation is minimal.
« If all compressors are similar, the pressure setting can be adjusted such that only one compressor handles the load variation, whereas the others operate more or less at full load. 
« If compressors are of different sizes, the pressure switch should be set such that only the smallest compressor is allowed to modulate (vary in flow rate). 
« If different types of compressors are operated together, unload power consumptions are significant. The compressor with lowest no load power must be modulated.
« In general, the compressor with lower part load power consumption should be modulated. «Compressors can be graded according to their specific energy consumption, at different pressures and energy efficient ones must be made to meet most of the demand (see Table 3.10)   
EXAMPLE 
Compressor modulation Assessing compressed air system study for a plant section gave following results. Comment on the results?  
«Compressors on line A, B, C, D, E (all reciprocating type)
« Trial observation Summary
Comments: 
For a cycle time of 45 minutes (39.12 + 5.88) 
1) Compressed air generated in m3
 = 45 (13.17) + 45 (12.32) + 45 (13.14) + 45 (12.75) + 5.88 (13.65) 
 = 2392.36 m3 

ii) Power consumption kWh
=45/60(115.3)=45/60(117.20)=45/60(108.3)=45/60(104.3)=5.88/60(109.30)=39.12/60(39.3)
=370.21 kWh/45mint.

iii)Compressed air generation actual capacity on line in m3
= 45 [13.17 + 12.32 + 13.14 + 12.75 + 13.65]
= 2926.35 m3

a)The consumption rate of the section connected
= 2392.36 / 45
= 53.16 m3/minute 
b)Compressor air drawl as a % of capacity on line is 
 = [2392.36 / 2926.35 | x 100 
 = 81.75 % 
c)Specific power consumption 
= 370.21 / 2392.36 
= 0.155 kW/m3 
d)Idle power consumption due to unload operation 
= 25.62 [=39.12 x 39.3 / 60] kWh in every 45 minutes cycle i.e., 34.16 [=25.62 x 60 / 45] kWh every hour. 
e) It would be favourable in short term and energy efficient to keep the compressor ‘D’ in cycling mode on account of lower un-load losses and hence capacity. Speed of the compressor can also be reduced by reducing motor pulley size. 
f) A suitable smaller capacity compressor can be planned to replace the compressor with highest unload losses. 
g) An investigation is called for, as to why such a large variation of unload power drawn, exists although all compressors have almost the same rated capacity.    

Segregating low and high pressure air requirements 
If the low-pressure air requirement is considerable, it is advisable to generate low pressure and high pressure air separately, and feed to the respective sections instead of reducing the pressure through pressure reducing valves, which invariably waste energy. 

Minimum pressure drop in air lines 
Pressure drop in air lines is depending upon the quantity of airflow, diameter of the pipeline, pipe length and pipe geometry i.e. the bends in the pipe lines.-Excess pressure drop due to inadequate pipe sizing, choked filter elements, improperly sized couplings and hoses represent energy wastage  
The pipelines should be with minimum number of Joints, bends and fittings. Further to minimize the joints, it should be ensured that joints are welded instead of flexible or screwed joints. This facilitates minimizing the leakages and pressure drop. 
Typical acceptable pressure drop in industrial practice is 0.3 bar in mains header at the farthest point and 0.5 bar in distribution system. 
The Table 3.11 illustrates the energy wastage, if the pipes are of smaller diameter.
Equivalent lengths of fittings Not only piping, but also fitting are a source of pressure *losses. Typical pressure losses for various fitting are given in Table 3.12.

Blowers in place of Compressed Air System
Since the compressed air system is already available, plant engineer may be tempted to use compressed air to provide air for low-pressure applications such as agitation, pneumatic conveying or combustion air. Using a blower that is designed for lower pressure operation will cost only a fraction of compressed air generation energy and cost. 

Capacity Control of Compressors 
In many installations, the use of air is intermittent. Therefore, some means of controlling the output flow from the compressor is necessary. The type of capacity control chosen has a direct impact on the compressor power consumption. Some control schemes commonly used are discussed below: 

Automatic On / Off Control: 
Automatic On /Off control,as its name implies, starts or stops the compressor by means of a pressure activated switch as the air demand varies. This is a very efficient method of controlling the capacity of compressor, where the motor idle-running losses are eliminated, as it completely switches off the motor when the set pressure is reached. This control is suitable for small compressors. 

Load and Unload 
This is a two-step control where compressor is loaded when there is air demand and unloaded when there is no air demand. During unloading, a positive displacement compressor may consume up to 30 % of the full load power, depending upon the type, configuration, operation and maintenance practices. 

Multi-step Control 
Large capacity reciprocating compressors are usually equipped with a multi-step control. In this type of control, unloading is accomplished in a series of   steps, (0%, 25 %, 50 %, 75 % & 100 %) varying from full load down to no-load (see Table 3.13).
Throttling Control
The capacity of centrifugal compressors can be controlled using variable inlet guide vanes. However, another efficient way to match compressor output to meet varying load requirements is by speed control (see Table 3.14). 
At low volumetric flow (below 40 %), vane control may result in lower power input compared to speed control due to low efficiency of the speed control system. For loads more than 40 %, speed control is recommended. 

Avoiding Misuse of Compressed Air: 
Misuse of compressed air for purposes like body cleaning, liquid agitation, floor cleaning, drying, equipment cooling and other similar uses must be discouraged. Wherever possible, low-pressure air from a blower should be substituted for compressed air, for example secondary air for combustion in a boiler / furnace. 
The following Table 3.15 gives an idea of savings by stopping use of compressed air by choosing alternative methods to perform the same task.
° Electric motors can serve more efficiently than air-driven rotary devices, wherever applicable. The Table gives the comparison of pneumatic grinders and electrical grinders. 
 It may be noted that in some areas use of electric tools are not permitted due to safety constraints, especially places where inflammable vapours are present in the environment. It should always be remembered that safety consideration always overrides energy conservation.

1. In place of pneumatic hoists, electric hoists can be used. 
2. Material conveying applications by blower systems can be replaced preferably by a combination of belt / screw conveyers and bucket elevators. In a paper manufacturing facility, compressed air was used for conveying wood chips. The equivalent power consumption was 77 kW. This method of conveying was replaced by blower system consuming only 7 kW, a saving of 70 kW. This has also been widely applied in cement industry where pneumatic conveying has been replaced by bucket and screw conveyor resulting in significant energy reduction.
3.When moving air really is required for an application, often sources other than compressed air can do the job. For applications like blowing of components, use of compressed air amplifiers  (see Figure 3.7), blowers or gravity-based systems may be possible. Brushes can sweep away debris from work in progress as effectively as high-pressure air. Blowers can also be used for this purpose. Many applications do not require clean, dry, high-pressure and expensive 6 bar or 7 bar compressed air rather, only moving air is needed to blow away debris, provide cooling, or other functions. In these cases, local air fans or blowers may satisfy the need for moving air much economically. If a 4” hose pipe is kept open at a 7 bar compressed air line for cleaning for at least 1000 hours / annum, it can cost about Rs. 1.0 lakhs / annum. If absolutely necessary, compressed air should be used only with blow guns to keep the air pressure below 2 bar.
4. For applications, where compressed air is indispensable for cleaning internal crevices of machines etc., installation of a separate cleaning air header with a main isolation valve may be considered. The main valve should be opened only for a few, well-defined time periods during the whole day; no connections for cleaning should be provided from process or equipment air lines. 
5. Replacement of pneumatically operated air cylinders by hydraulic power packs can be considered. . 6.Vacuum systems are much more efficient than expensive venturi methods, which use expensive compressed air rushing past an orifice to create a vacuum. 
7 . Mechanical stirrers, conveyers, and low-pressure air will mix materials far more economically than high-pressure compressed air. 
 
Avoiding Air Leaks and Energy Wastage: 
The major opportunity to save energy is in the prevention of leaks in the compressed air system. Leaks frequently occur at air receivers, relief valves, pipe and hose joints, shut off valves, quick release couplings, tools and equipment. In most cases, they are due to poor maintenance and sometimes, improper installations etc. 

Air leakages through Different Size Orifices 
The Table 3.16 gives the amount of free air wasted for different nozzles sizes and pressure.  
  
Cost of Compressed Air Leakage:
It may be seen from Table 3.17 that any expenditure on stopping leaks would be paid back through energy saving.  
Steps in simple shop-floor method for leak quantification 
1. Shut off compressed air operated equipments (or conduct test when no equipment is using compressed air).
2. Run the compressor to charge the system to set pressure of operation 
3. Note the sub-sequent time taken for ‘load’ and ‘unload’ cycles of the compressors. For accuracy, take ON & OFF times for 8 — 10 cycles continuously.
4.Then calculate total ‘ON’ Time (T) and Total ‘OFF’ time (t). . The system leakage is calculated as: 
Where,
Q = Compressor capacity (m/min) 
T = Time on load in minutes 
 t = Time on unload in minutes

EXAMPLE
In the leakage test in a process industry, following results were observed 
Compressor capacity (m3/minute) = 35 
Cut in pressure, kg/cm2(g) = 68 
Cut out pressure, kg/cm2(g) = 75 
Load kW drawn = 188kW 
Unload kW drawn = 54kW 
Average ‘Load’ time, T = 1.5 minutes 
Average ‘Unload’ time, t = 10.5 minutes 
Comment on leakage quantity and avoidable loss of power due to air leakages. 
Leakage Detection by Ultrasonic Leak Detector 
Leakage tests are conducted by a Leak Detector having a sensing probe, which senses when there are leakages in compressed air systems at high temperatures-beneath insulated coverings, pipelines, manifolds etc.
The leak is detected by ultrasonic vibration. Leak testing is done by observing and locating sources of ultrasonic vibrations created by turbulent flow of gases passing through leaks in pressurized or evacuated systems.

Line Moisture Separator and Traps 
Although, in an ideal system, all cooling and condensing of air should be carried out before the air leaves the receiver, this is not very often achieved in practice. The amount of condensation, which takes place in the lines, depends on the efficiency of moisture extraction before the air leaves the receiver and the temperature in the mains itself. In general, the air main should be given a fall of not less than 1 m in 100 m in the direction of air flow, and the distance between drainage points should not exceed 30m. 
Drainage points should be provided using equal tees, as it assists in the separation of water. Whenever a branch line is taken off from the mains it should leave at the top so that any water in the main does not fall straight into the plant equipment. Further, the bottom of the falling pipe should also be drained.

Compressed Air Filter 
Although, some water, oil and dirt are removed by the separators and traps in the mains, still some are always left, which are carried over along with compressed air. Moreover, pipe systems accumulate scale and other foreign matters, such as small pieces of gasket material, jointing compounds etc. Burnt compressor oil may also be carried over in pipe work, and this, with other contaminants, forms a gummy substance. To remove these, all of which are liable to have harmful effects on pneumatic equipment, the air should be filtered as near as possible to the point of use. Water and oil collected in the filter sump must be drained off; because if the level is allowed to build up, it is forced through the filter element into the very system for which it is designed to protect.   

Regulators 
In many instances, pneumatic operations are to be carried out at a lower pressure than that of the main supply. For these applications, pressure regulators are required to reduce the pressure to the required value and also to ensure that it remains reasonably constant at the usage point.

Lubricators
Where air is used to drive prime movers, cylinders and valves, they should be fitted with a lubricator. Essentially, a lubricator is a reservoir of oil and has been designed so that when air is flowing, a metered amount of oil is fed in mist form into the air stream. This oil is carried with the motive air, to the point of use to lubricate all moving parts. All lubricators require a certain minimum rate of airflow to induce oil into their stream. It is advisable to install filters, regulators and lubricators as close as possible to the equipment being served.  

Air Dryers 
The atmospheric air has certain amount of moisture. The moisture holding capacity of air depends on the ambient temperature. Higher the temperature more is the moisture holding capacity of air in the form of water vapour and vice versa. Saturated air at a given temperature is the air that contains the maximum amount of water in the form of water vapour. Any excess water vapour will be condensed in the form of water. 
About 60 to 75% of moisture in compressed air is removed at the after cooler. This is sufficient for many plant air applications such as cleaning, atomisation etc. As compressed air leaves the after cooler and passes through the compressed air lines, the temperature of the compressed air further reduces. The remaining water vapour in the air starts condensing.
The effects of water particles in the compressed air are given below. 
. The water particles travel at the same velocity of compressed air and damages the pneumatic valves or instruments at the user ends by erosion. 
. Corrosion in the distribution pipe work.
. Impaired finishing processes particularly in paint spraying, sheet cleaning etc.
Hence, the water vapour from the compressed air has to be removed, for applications such as instrumentation and pneumatics. This can be achieved by passing the compressed air through the air dryers.
The extent of drying compressed air is expressed by the term “Atmospheric Dew Point” which is the temperature at which moisture present in the air starts condensing at atmospheric pressure. Lower the dew point, more dry is the air. Air at -40°C atmospheric dew point means no moisture would condense unless temperature of the air is reduced to less than — 40°C, at atmospheric pressure. 
The moisture content corresponding to various atmospheric dew points is shown in the table 3.18 below: 
The performance of a dryer is quoted in terms of “pressure dew point’ and there is a relation between both dew points.
Increasing the pressure of a gas increases the dew point temperature of the gas. For example, air at atmospheric pressure of 1013.3 mbar has a dew point temperature of -10 °C. Corresponding partial pressure of water vapour is 2.8 mbar. If this air is compressed and the total pressure is doubled to 2026.6 mbar, then according to Dalton’s law, the partial pressure of water vapour is also doubled to the value of 5.6 mbar. The dew point temperature corresponding to 5.6 mbar is approximately -1 °C, so it is clear that increasing the pressure of the air also increases the dew point temperature of the air.   

Most commonly used dryers in the industry are:
1. Refrigerant type and 
2. Adsorption type - can be of the following type: 
(a) Blower reactivated type 
(b) Heatless purge type
(c) Heat of compression (HOC) type 
The principle of operation of different dryers are explained as follows. 

Refrigerant Dyers 
The system (Figure 3.8) is straight mechanical refrigeration in which the dew point of air is reduced by chilling.Additionally, a second heat exchanger is introduced wherein the outgoing cold air pre-cools the incoming compressed air. The compressed air leaves the system fully dry. The achievable dew point (atmospheric) in this kind of refrigerant dryer is -20°C.


Features:
1.Refrigeration drying is the most economical process of approximately 90 % of all applications.
2.Almost 100 % of all solid particles and water droplets larger than 3 um are separated.
3.The pressure loss from the dryer is approximately 0.2 bar.

Adsorption Drying
Drying compressed air by adsorption is a purely physical process. The moisture is bound to the drying
agent by force of adhesion (unbalanced molecular attraction). The moisture stays on the inner and
outer surfaces of the adsorption material without a chemical reaction taking place. The adsorption
material has an open porous structure and a large inner surface. The most common adsorption materials
used for compressed air drying are activated alumina and silica gel.

Operating principle
 During the drying process the moist compressed air flows through an adsorption tank. The moisture is bound, which dries the compressed air. This process generates heat. The adsorption material must be regenerated when the adhesive forces are balanced by water deposits. This means that the water must be removed from the adsorption material. For this reason there must be second parallel drying tank to maintain continual operation. The active tank A (Figure 3.9) dries the compressed air, while the inactive tank B regenerates without pressure. Based on the method of regeneration the adsorption dryers can be classified as follows,
Blower Reactivated Type Dryer
blower and external heater is used to achieve the regenerating temperature. The operating cost is higher because of the heater (electrical or steam) and also because there is a purge loss of about 1-2% of dry compressed air. The vessel which is regenerated is purged with dry air before it is taken into service. These dryers are normally used for capacities higher than 250 cfm. The schematic of the dryer is shown in Figure 3.10. Vessel ‘A’ is in service and vessel *B’ is in heating mode. Cooling is done after which vessel ‘B’ is taken into service and vessel ‘A’ goes into regeneration mode.

Heatless Purge Type Dryer
The operation is very similar to the blower reactivated type, only difference being that no heating of
the dessicant is done. Pure dry compressed air is used for purging through the saturated dessicant.
These are used for capacities less than 250 cfm. The operating cost is very high due to purge losses of
about 12-15%. The schematic of the dryer is shown in Figure 3.11.

Heat of Compression (HOC) Dryer
This is a break-through in drying technology where the operating cost is zero or very minimal. HOC dryers are available from 400 cfm to 5000 cfm capacity. Compressed air, directly from compressor discharge (before after cooler), which is at a temperature of 135°C (in the case of reciprocating compressor) is used to regenerate the dessicant. There are no electrical heaters and no purging loss. This makes the dryer very attractive in terms of operating cost.
The dryer consists of two vessels - ‘A’ and ‘B’. Vessel ‘A’ will be in service for 4 hours. Meanwhile vessel ‘B’ is reactivated which consists of heating for 2 1/2 hrs and cooling for 1 1/2 hrs. After this, vessel ‘B’ is taken into service and vessel ‘A’ is reactivated. The regeneration cycle consisting of heating and cooling cycle as explained as follows

a. Vessel ‘A’in service, vessel ‘B’in heating 
Air from compressor enters 4-way valves V2 and V1 (Figure 3.12 (a)) and directly to vessel ‘B’ so as to start the heating process. From vessel ‘B’ the air through valve  V3 and V2 enters after cooler AC1, where it loses some of the moisture. Through V3 again air enters vessel 'A’where moisture is adsorbed by the dessicant and finally leaves through V1 to an After-cooler AC2 where it is A cooled to about 35-40 °C. After getting filtered in the After-filter, air goes to process which is dry to an atmospheric dew point of -40 °C. The heating cycle is normally for 2 1/2 hours duration.:

b. Vessel ‘A’ in service, vessel ‘B’in cooling
Air from compressor passes through V2 (Figure 3.12 (b)), gets cooled in AC1 and enters vessel ‘B’ through V3. After cooling the dessicant in vessel ‘B’ air passes through 4-way valves V1, V2 and V3 and enters vessel “A’, which is in service. The air on getting dry, enters After-cooler AC2 via V1, gets cooled to about 35-40°C. This air dryed to an atmospheric dew point of -40°C is now ready for use. The cooling cycle is normally for about 11/2 hour duration.
'image.png' failed to upload.
Membrane Dryers 
Membrane dryers use the process of selective permeation of the gas components in the air. The dryer
is a cylinder which houses thousands of tiny hollow polymer fibers with an inner coating. These fibers
have selective permeation for the removal of water vapor. As filtered, wet compressed air enters the
cylinder, the membrane coating allows water vapor to permeate the membrane wall and collect between
the fibers, while the dry air continues through the fibers in the cylinder at almost the same pressure as
the incoming wet air. The permeated water is vented to the atmosphere outside of the cylinder.
The permeation or separation is caused by the difference in the partial pressure of a gas between the
inside and the outside of the hollow fiber.
Membrane dryers (Figure 3.13) are simple to operate, silent while operating, have no moving parts,
low power consumption and minimal service requirements (mainly filters upstream of the dryer).

Refer Table 3.19 for typical dew point and power consumption data for dryers.

Air Receivers
The air receiver dampens pulsations entering the discharge from the compressor, serves as a reservoir
for sudden or unusually heavy demands in excess of compressor capacity, prevents too frequent loading
and unloading (short cycling) of the compressor and separates moisture and oil vapour, allowing the
moisture carried over from the after coolers to precipitate.
The air receiver should be generously sized to give a large cooling surface and even out the pulsation
in delivered air pressure from reciprocating compressor. As per IS 7938 — 1976, volume of the air
receiver (in/m3) should be 1/10" to 1/6" of output in m3/min. Providing an air receiver near the load
end, where there is sudden high demand lasting for a short period, would avoid the need to provide
extra compressor capacity.

Sizing of compressed air piping
The compressed air piping is sized based on the allowable velocity of compressed air in the pipeline,
keeping a check on the pressure drop. In compressed air line if the pressure drop is high, the
operating pressure at the generation end has to be increased to match with the requirement. This will
result in increased power consumption of the compressor.
Velocities between 6 to 10 m/sec are usual in compressed air mains. This velocity range is sufficiently
low to prevent excessive pressure drops on most systems and also will allow moisture to precipitate.
The volume of air changes if any of the following changes.
¢ Operating Pressure
¢ Temperature
¢ Both Pressure and Temperature
The law dealing with the expansion of air wherein pressure and temperature are changing together is
given below.

P1*V1/T1 = P2*V2T2
Where P1 V1 and T1 are the original pressure, volume and temperature and P2 V2 and T2 are the
new pressure, volume and temperature respectively.
The following procedure can be adopted for estimating the size of a compressed air line.
Loss of air pressure due to friction
The loss of pressure in piping is caused by resistance in pipe fittings and valves, which dissipates
energy by producing turbulence. The piping system will be designed for a maximum allowable pressure
drop of 5 percent from the compressor to the most distant point of use.

Piping layout
Where possible the piping system should be arranged as a closed loop or “ring main” to allow for more
uniform air distribution to consumption points and to equalize pressure in the piping. Separate services
requiring heavy air consumption and at long distances from the compressor unit should be supplied by separate main airlines. Pipes are to be installed parallel with the lines of the building, with main and branch headers sloping down toward a dead end. Traps will be installed in airlines at all low points and dead ends to remove condensed moisture. Automatic moisture traps used for this purpose are effective only when the air has been cooled and the moisture has precipitated. Branch headers from compressed air mains will be taken off at the top to avoid picking up moisture.

Capacity Utilisation
In many installations, the use of air is intermittent. This means the compressor will be operated on
low load or no load condition, which increases the specific power consumption per unit of air generated.
Hence, for optimum energy consumption, a proper compressor capacity control should be selected. The nature of the control device depends on the function to be regulated. One of the objectives of a good compressed air management system would be to minimize unloading to the least as unloading consumes up to 30% of full load power.

One way of doing this is to use a smaller compressor.
Decentralized compressors, as against centralized compressors often serve this purpose better by
having the option to switch off when air is not need in a particular section/equipment. If a compressor is oversized and operates at unloading mode for long periods, an economical way will be to suitably change the pulley size of the motor or compressor and reduce the RPM to de-rate the compressor to a lower capacity.
With decreasing cost of variable speed drives, it has become a viable option to maintain constant
pressure in the system and to avoid unloading operations by varying the speed of the compressor.
However, caution should be taken for operations at very low speeds, since it will affect the lubricating
system. This can be overcome by providing a separate lube oil system independent of the compressor.

Compressor Capacity Assessment
Due to ageing of the compressors and inherent inefficiencies in the internal components, the free air delivered may be less than the design value, despite good maintenance practices. Sometimes, other factors such as poor maintenance, fouled heat exchanger and effects of altitude also tend to reduce free air delivery. In order to meet the air demand, the inefficient compressor may have to run for more time, thus consuming more power than actually required.

The power wastage depends on the percentage deviation of FAD capacity. For example, a worn out compressor valve can reduce the compressor capacity by as much as 20 percent. A periodic assessment
of the FAD capacity of each compressor has to be carried out to check its actual capacity. If the deviations are more than 10 %, corrective measures should be taken to rectify the same. The ideal method of compressor capacity assessment is through a nozzle test wherein a calibrated nozzle is used as a load, to vent out the generated compressed air. Flow is assessed, based on the air temperature, stabilization pressure, orifice constant etc.

Simple method of Capacity Assessment in Shop floor
Isolate the compressor along with its individual receiver being taken for test from main compressed
air system by tightly closing the isolation valve or blanking it, thus closing the receiver outlet.
Open water drain valve and drain out water fully and empty the receiver and the pipe line. Make sure
that water trap line is tightly closed once again to start the test. Start the compressor and activate the
stopwatch. Note the time taken to attain the normal operational pressure P2 (in the receiver) from initial
pressure P1
Calculate the capacity as per the formulae given below:

Actual Free air discharge
The above equation is relevant where the compressed air temperature is same as the ambient air
temperature, i.e., perfect isothermal compression. In case the actual compressed air temperature at
discharge, say t2°C is higher than ambient air temperature say t1°C (as is usual case), the FAD is to be
corrected by a factor (273 + t1) / (273 +t2).

EXAMPLE 1
An instrument air compressor capacity test gave the following results (assume the final compressed
air temperature is same as the ambient temperature) - Comment?
Piston displacement                       :                       16.88 m3/minute
Theoretical compressor capacity   :                       14.75 m3/minute @ 7 kg/cm2
Compressor rated rpm 750            :                       Motor rated rpm : 1445
Receiver Volume                           :                     7.79 m3
Additional hold up volume,
1.e., pipe / water cooler, etc., is     :                        0.4974 m3
Total volume                                  :                       7.79+0.4974 =8.287 m3
Initial pressure P1                          :                        0.5 kg/cm2
Final pressure  P,,                           :                       7.03 kg/cm2
Atmospheric pressure P0               :                       1.026 kgf/cm’A
Time taken to build up pressure    :                        4.021 minutes
Capacity shortfall with respect to 14.75 m3/minute rating is 1.63 m3/minute i.e., 11.05 %, which indicates compressor performance needs to be investigated further.

Checklist for Energy Efficiency in Compressed Air System
1.Ensure air intake to compressor is not warm and humid by locating compressors in
well-ventilated area or by drawing cold air from outside. Every 4°C rise in air inlet
temperature will increase power consumption by percent.
2.Clean air-inlet filters regularly. Compressor efficiency will be reduced by 2 percent for
every 250 mm WC pressure drop across the filter.
3.Keep compressor valves in good condition by removing and inspecting once every six
months. Worn-out valves can reduce compressor efficiency by as much as 50 percent.
4.Install manometers across the filter and monitor the pressure drop as a guide to
replacement of element.
5.Minimize low-load compressor operation; if air demand is less than 50 percent of
compressor capacity, consider change over to a smaller compressor or reduce compressor
speed appropriately (by reducing motor pulley size) in case of belt driven compressors.
6.Consider the use of regenerative air dryers, which uses the heat of compressed air to
remove moisture.
7.Fouled inter-coolers reduce compressor efficiency and cause more water condensation
in air receivers and distribution lines resulting in increased corrosion. Periodic cleaning
of inter-coolers must be ensured.
8.Compressor free air delivery test (FAD) must be done periodically to check the present
operating capacity against its design capacity and corrective steps must be taken if
required.
9.If more than one compressor is feeding to a common header, compressors must be
operated in such a way that only one small compressor should handle the load variations
whereas other compressors will operate at full load.
10.The possibility of heat recovery from hot compressed air to generate hot air or water for
process application must be economically analyzed in case of large compressors.
11.Consideration should be given to two-stage or multistage compressor as it consumes less
power for the same air output than a single stage compressor.
12.If pressure requirements for processes are widely different (e.g. 3 bar to 7 bar), it is
advisable to have two separate compressed air systems.
13.Reduce compressor delivery pressure, wherever possible, to save energy.
14.Provide extra air receivers at points of high cyclic-air demand which permits operation
without extra compressor capacity.
15Retrofit with variable speed drives in big compressors, say over 100 kW, to eliminate the
‘unloaded’ running condition altogether.
16. Keep the minimum possible range between load and unload pressure settings.
17. Automatic timer controlled drain traps wastes compressed air every time the valve
opens. So frequency of drainage should be optimized.
18. Check air compressor logs regularly for abnormal readings, especially motor current
cooling water flow and temperature, inter-stage and discharge pressures and temperatures
and compressor load-cycle.
19. Compressed air leakage of 40- 50 percent is not uncommon. Carry out periodic leak tests
to estimate the quantity of leakage.
20. Install equipment interlocked solenoid cut-off valves in the air system so that air supply
to a machine can be switched off when not in use.
21. Present energy prices justify liberal designs of pipeline sizes to reduce pressure drops.
22. Compressed air piping layout should be made preferably as a ring main to provide
desired pressures for all users.
23. A smaller dedicated compressor can be installed at load point, located far off from the
central compressor house, instead of supplying air through lengthy pipelines.
24. All pneumatic equipment should be properly lubricated, which will reduce friction,
prevent wear of seals and other rubber parts thus preventing energy wastage due to
excessive air consumption or leakage.
25. Misuse of compressed air such as for body cleaning, agitation, general floor cleaning,
and other similar applications must be discouraged in order to save compressed air and
energy.
" Pneumatic equipment should not be operated above the recommended operating pressure
as this not only wastes energy but can also lead to excessive wear of equipment’s
components which leads to further energy wastage.
26. Pneumatic transport can be replaced by mechanical system as the former consumed about
8 times more energy. Highest possibility of energy savings is by reducing compressed
air use.
27. Pneumatic tools such as drill and grinders consume about 20 times more energy than
motor driven tools. Hence they have to be used efficiently. Wherever possible, they
should be replaced with electrically operated tools.
28. Where possible welding is a good practice and should be preferred over threaded
connections.
29. On account of high pressure drop, ball or plug or gate valves are preferable over globe
valves in compressed air lines.

Solved Example:
a) In an automobile industry a pump-up test was conducted to determine the free air delivery (FAD)
of a reciprocating compressor and the following data were obtained:
Receiver capacity and additional holdup volume
in piping and after-cooler                    :                     4100 litres
Initial pressure                                     :                    1 kg/cm2 (g)
Final pressure                                      :                     8.5 kg/cm2 (g)
Atmospheric Pressure                         :                    1.026 kg/cm2 (a)
Ambient air temperature                     :                    32°C
Final compressed air temperature       :                    52 °C
Compressor pump up time                  :                   65 secs
Calculate the FAD of the compressor in cubic foot per minute.

b) Further a leakage test was carried out in the same compressed air system and with the same compressor
as in problem a) above and following were the observations:
- Compressor was on load for 03 minutes
- Compressor was unloaded for 13 minutes
- Compressor was drawing 145 kW during load
Calculate the following:
i. % leakage in compressed air system
li. Leakage quantity
iii. Specific power consumption
iv. Power lost due to leakage

----------------------------------


Comments

Followers

Popular posts from this blog

Welder qualification procedure as per ASME Sec IX

  WELDER QUALIFICATON PROCEDURE (FOR PLATE &PIPING) 1.      Test positions for performance qualification 1.1   Positions (Groove weld) plate & pipe: - An angular deviation of plus or minus 15° From specified horizontal and vertical planes is permitted during welding. Position for qualification as per ASME IX QW-461.3 & QW-461.4 Table. 1 Plate Positions Pipe Positions a)        Vertical Position 3G (Fig.1a) b)        Overhead Positions 6G- (Fig.1b)   b) Overhead Position 4G (Fig.1a)               Fig. 1 Position of test peace for Groove weld (Plate & Pipe). 1.2   Test Positions for Fillet Welds: - An angular deviation of plus or minus 15° from the specified horizontal and vertical planes is permitted during welding. Position for qualification as per ASME QW-461.5 Table.2 Fillet joint Positions         a)   Vertical 3F        b)

Lathe machine

                                                       TYPES OF LATHE  Lathes are manufactured in a variety of types and sizes, from very small bench lathes used for precision work to huge lathes used for turning large steel shafts. But the principle of operation and function of all types of lathes is same. The different types of lathes are: 1. Speed lathe ( a ) Wood working ( b ) Spinning ( c ) Centering ( d ) Po1ishing   2. Centre or engine lathe ( a ) Be1t drive ( b ) Individual motor drive ( c ) Gear head lathe   3. Bench lathe   4. Tool room Lathe   5. Capstan and Turret 1athe   6. Special purpose lathe ( a ) Whee1 lathe ( b ) Gap bed lathe ( c ) Dup1icating lathe ( d ) T-lathe   7.Automatic lathe Speed Lathe Speed lathe is simplest of all types of lathes in construction and operation. The important parts of speed lathe are following- (1) Bed (2) Headstock (3) Tailstock, and (4) Tool post mounted on an adjustable slide.   It has no

Minimum required thickness of process pipeline (Engineering calculation)

Pressure Calculation Calculator:Minimum required thickness of pipeline for service as per ASME B31.3 Design Pressure (PSI): Diameter (inch): Stress 'S' (PSI): Quality Factor 'E': Weld Joint Reduction Factor 'W': Coefficient 'Y': Calculate Results: Min. Reqired Thickness tm (inch): 12.5% Allowance (inch): Mini. Required Thicknes (mm): After getting 12.5% allowance (inch) value again check ASME B36.10 or API 574 piping thickness table and choose thicknes value higher then this value for service. Calculating the Minimum Required Thickness of Pipelines for Service as per ASME B31.3 Introduction: In the field of engineering, designing safe and reliable pipelines is of utmost importance. The American Society of Mechanical Engineers (ASME) B31.3 code provides guidelines for the design and construction of process piping systems. One cr

Ultrasonic Flaw Detection: Unveiling the Power of Sound in Non-Destructive Testing

Introduction: Non-destructive testing (NDT) techniques play a vital role in ensuring the integrity and safety of structures, materials, and components in various industries. Among the array of NDT methods available, ultrasonic flaw detection stands out as a powerful and versatile technique. In this blog, we will explore the fundamentals of ultrasonic flaw detection, its applications, and the benefits it offers in detecting and characterizing defects without causing damage. Join us as we dive into the world of sound waves and their ability to reveal hidden flaws. 1. Understanding Ultrasonic Flaw Detection: 1.1 The Basics of Ultrasonics: We'll introduce the principles of ultrasonics, explaining how sound waves are generated, propagated, and detected. 1.2 Interaction with Materials: We'll explore how ultrasonic waves interact with different materials, including their reflection, transmission, and absorption behaviors. 2. How Ultrasonic Flaw Detection Works: 2.1 Transducers: We'

Calculator: Remaining Thickness of Pressure vessel API 510 (Identify remaining thickness is safe/unsafe)

Thickness Calculation Remaining Thickness of Pressure vessel to identify safe for service Design Pressure (psi): Radius (inch): Stress (psi) ASME Sec VIII Div 1: Efficiency 'E': T(nominal) (inch): Metal Loss (inch): Calculate   Remaining Thickness of Pressure vessel API 510  (Identify remaining thickness is safe/unsafe) Introduction: In the field of pressure vessel inspection and maintenance, determining the remaining thickness of the vessel is of utmost importance. This calculation helps assess the structural integrity of the vessel and ensures its safe operation. In this blog post, we will explore the method for calculating the remaining thickness of a pressure vessel as per API 510 standards. Formula for Minimum Thickness (Tmin): The API 510 standard

Purging Gas in Gas Tungsten Arc Welding: Enhancing Weld Quality and Integrity

Introduction: In the realm of welding, achieving high-quality welds with excellent integrity is paramount. One crucial technique that aids in this endeavor is the use of purging gas. Purging gas plays a vital role in preventing oxidation and ensuring a clean, controlled environment during welding. In this blog, we will explore the significance of purging gas, its purpose, techniques, and benefits in various welding applications. Join us as we delve into the world of purging gas and its impact on weld quality. Back purging is most important phenomenon in GTAW process because this process is mostly used in Stainless steel. Stainless steel is widely used fabrication of chemical, petrochemical, food etc. plant. All thin section and root welding is performed by GTAW process. GTAW process is also very popular in Aluminum welding. In all large diameter pipe the root pass welding is done by GTAW process where the back purging is mandatory. Purging gas protect the weld metal fro

Energy efficiency in Thermal utilities (Chapter 3: Steam System)

  Energy efficiency in Thermal utilities  (Chapter 3: Steam System) Introduction  Steam has been a popular mode of conveying energy since the industrial revolution. Steam is used for generating power and also used in process industries such as sugar, paper, fertilizer, refineries, petrochemicals, chemical, food, synthetic fiber and textiles. The following characteristics of steam make it so popular and useful to the industry:  ¢ Highest specific heat and latent heat ¢ Highest heat transfer coefficient e Easy to control and distribute Cheap and inert   Properties of Steam  Water can exist in the form of solid, liquid and gas as ice, water and steam respectively. If heat energy is added to water, its temperature rises until a value is reached at which the water can no longer exist as a liquid. We call this the “saturation” point and with any further addition of energy, some of the water will boil off as steam. This evaporation requires relatively large amounts of energy, and whil