ENERGY_EFFICIENCY_IN_ELECTRICAL_UTILITIES
(Chapter 2: Electric Motors)
Introduction
Motors convert electrical energy into mechanical energy by the interaction between the magnetic fields
set up in the stator and rotor windings. Industrial electric motors can be broadly classified as induction
motors, direct current motors or synchronous motors. All motor types have the same four operating
components: stator (stationary windings), rotor (rotating windings), bearings, and frame (enclosure).
Motor Types
Induction Motors
An AC induction motor (Figure 2.1) has a fixed outer
portion, called the stator and a rotor that spins inside with
a carefully engineered air gap between the two. Ifa 3-phase supply is fed to the stator windings of a 3-phase
motor, a magnetic flux of constant magnitude, rotating at
synchronous speed is set up. At this point, the rotor is
stationary. The rotating magnetic flux passes through the
air gap between the stator & rotor and sweeps past the
stationary rotor conductors. This rotating flux, as it sweeps,
cuts the rotor conductors, thus causing an e.m.f to be
induced in the rotor conductors. As per the Faraday's law
of electromagnetic induction, it is this relative motion between the rotating magnetic flux and the stationary rotor conductors, which induces an e.m.f on the
rotor conductors. Since the rotor conductors are shorted and form a closed circuit, the induced e.m.f
produces a rotor current whose direction is given by Lenz s Law, is such as to oppose the cause producing
it. In this case, the cause which produces the rotor current is the relative motion between the rotating
magnetic flux and the stationary rotor conductors. Thus to reduce the relative speed, the rotor starts to
rotate in the same direction as that of the rotating flux on the stator windings, trying to catch it up. The
frequency of the induced e.m.f is same as the supply frequency.
The magnetic field produced in the rotor because of the induced voltage is alternating in nature. To reduce the relative speed, with respect to the stator, the rotor starts running in the same direction as that of the stator flux and tries to catch up with the rotating flux. However, in practice, the rotor never succeeds in “catching up” to the stator field. The rotor runs slower than the speed of the stator field.
The windings on the rotor of a squirrel cage motor is comprised of aluminum (or sometimes copper)
bars embedded in the steel laminations of the rotor. The ends of the rotor bars are shorted together by
rings at each end of the rotor. There is no external electrical connection to the rotor. The bar and ring
structure looks like an exercise wheel for a pet squirrel.
Slip-ring motor
The slip-ring motor or wound-rotor motor is a variation of the squirrel cage induction motor. While
the stator is the same as that of the squirrel cage motor, the rotor of a slip-ring motor is wound with
wire coils. The ends of the windings are connected to slip rings so that resistors or other circuitry can
be inserted in series with the rotor coils through carbon brushes that slide on the slip-rings allowing
an electrical connection with the rotating coils. This basically is the difference in construction between
a squirrel cage and slip-ring motors. These are helpful in adding external resistors and contactors. The
slip necessary to generate the maximum torque (pull-out torque) is directly proportional to the rotor
resistance.
In the slip-ring motor, the effective rotor resistance is increased by adding external resistance
through the slip rings. Thus, it is possible to get higher slip and hence, the pull-out torque at a lower
speed. A particularly high resistance can result in the pull-out torque occurring at almost zero speed,
providing a very high pull-out torque at a low starting current. As the motor accelerates, the value of
the resistance can be reduced, altering the motor characteristic to suit the load requirement. Once the
motor reaches the base speed, external resistors are removed from the rotor.
This means that now the
motor is working as the standard induction motor.
This motor type is ideal for very high inertia loads, where it is required to generate the pull-out torque
at almost zero speed and accelerate to full speed in the minimum time with minimum current draw.
Modifying the speed torque curve by altering the rotor resistors, the speed at which the motor will
drive a particular load can be altered. At full load the speed can be reduced effectively to about 50%
of the motor synchronous speed, particularly when driving variable torque/variable speed loads, such
as printing presses, compressors, conveyer belts, hoists and elevators. Reducing the speed below 50%,
results in very low efficiency due to higher power dissipation in the rotor resistances. This type of
motor is used in applications for driving variable torque/ variable speed loads.
Direct-Current Motors
Direct-Current motors, as the name implies, use direct-unidirectional, current. Direct current motors
are used in special applications- where high torque starting or where smooth acceleration over a broad
speed range is required.
Synchronous Motors
AC power is fed to the stator of the synchronous motor. The rotor is fed by DC from a separate source.
The rotor magnetic field locks onto the stator rotating magnetic field and rotates at the same speed.
The speed of the rotor is a function of the supply frequency and the number of magnetic poles in the
stator. While induction motors rotate with a slip, i.e., rpm is less than the synchronous speed, the
synchronous motor rotate with no slip, i.e., the RPM is same as the synchronous speed governed by
supply frequency and number of poles. The slip energy is provided by the D.C. excitation power.
Permanent Magnet Synchronous Motor (PMSM)
The permanent magnet synchronous motor (PMSM) is an alternative for AC induction motors due to
various advantages such as power density, better cooling, smaller size, better efficiency and so on.
These PMSM’s have rotor structures similar to brushless DC motors which contain permanent magnets.
However, their stator structure is similar to Induction Motor wherein the windings are assembled such
that they produce a sinusoidal flux density in the air gap of the motor. As a result, these motors perform
best when driven by sinusoidal waveforms.
Synchronous Reluctance Motors
A synchronous reluctance motor has the same structure as that of a salient pole synchronous motor
except that it does not have a field winding on the rotor. These motors are becoming popular due its
superior performance and capable of achieving IE4 efficiency class. Synchronous reluctance Motors
Stator is similar to induction motors and permanent magnet synchronous motors (PMSMs) and its
rotor is built with simple magnetic materials to take advantage of the reluctance principle. The
Synchronous reluctance motor rotor runs at synchronous speed and there are no magnets or currentconducting parts in the rotor. Hence rotor losses are very small compared to those of an induction
motor.
Motor Characteristics
Motor Speed
The speed of a motor is the number of revolutions in a given time frame, typically revolutions per
minute (RPM). The speed of an AC motor depends on the frequency of the input power and the number
of poles for which the motor is wound. The synchronous speed in RPM is given by the following
equation, where the frequency is in hertz or cycles per second:
Indian motors have synchronous speeds like 3000 / 1500 / 1000 / 750 / 600 / 500 / 375 RPM
corresponding to no. of poles being 2, 4, 6, 8, 10, 12, 16 (always even) and given the mains frequency
of 50 cycles / sec.
The actual speed, with which the motor operates, will be less than the synchronous speed. The difference
between synchronous and full load speed is called slip and is measured in percent. It is calculated
using this equation:
As per relation stated above, the speed of an AC motor is determined by the number of motor poles and by the input frequency. It can also be seen that theoretically speed of an AC motor can be varied infinitely by changing the frequency. Manufacturer’s guidelines should be referred for practical limits to speed variation. With the addition of a Variable Frequency Drive (VFD), the speed of the motor can be decreased as well as increased.
As per relation stated above, the speed of an AC motor is determined by the number of motor poles and by the input frequency. It can also be seen that theoretically speed of an AC motor can be varied infinitely by changing the frequency. Manufacturer’s guidelines should be referred for practical limits to speed variation. With the addition of a Variable Frequency Drive (VFD), the speed of the motor can be decreased as well as increased.
Power Factor
kW
The power factor of the motor is given as: Power Factor
As the load on the motor comes down, the magnitude of the active current reduces. However, there
is no corresponding reduction in the magnetizing current, which is proportional to supply voltage
with the result that the motor power factor reduces, with a reduction in applied load. Induction motors,
especially those operating below their rated capacity, are the main reason for low power factor in
electric systems.
Motor Efficiency
Two important attributes relating to efficiency of electricity use by A.C. Induction motors are efficiency
(n), defined as the ratio of the mechanical energy delivered at the rotating shaft to the electrical energy
input at its terminals, and power factor (PF). Motors, like other inductive loads, are characterized by
power factors less than one. As a result, the total current draw needed to deliver the same real power
is higher than for a load characterized by a higher PF. An important effect of operating with a PF less
than one is that resistance losses in wiring upstream of the motor will be higher, since these are
proportional to the square of the current. Thus, both a high value for n and a PF close to unity are
desired for efficient overall operation in a plant.
Squirrel cage motors are normally more efficient than slip-ring motors, and higher-speed
motors are normally more efficient than lower-speed motors. Efficiency is also a function of motor
temperature. Totally-enclosed, fan-cooled (TEFC) motors are more efficient than screen-protected,
drip-proof (SPDP) motors. Also, as with most equipment, motor efficiency increases with the rated
capacity.
The efficiency of a motor is determined by intrinsic losses that can be reduced only by changes in
motor design. Intrinsic losses are of two types: fixed losses- independent of motor load, and variable
losses - dependent on load.
Fixed losses consist of magnetic core losses and friction and windage losses. Magnetic core losses (sometimes called iron losses) consist of eddy current and hysteresis losses in the stator. They vary with the core material and geometry and with input voltage.
Fixed losses consist of magnetic core losses and friction and windage losses. Magnetic core losses (sometimes called iron losses) consist of eddy current and hysteresis losses in the stator. They vary with the core material and geometry and with input voltage.
Friction and windage losses are caused by friction in the bearings of the motor and aerodynamic losses
associated with the ventilation fan and other rotating parts.
Variable losses consist of resistance losses in the stator and in the rotor and miscellaneous stray losses.
Resistance to current flow in the stator and rotor result in heat generation, that is proportional to the
resistance of the material and the square of the current (I’R). Stray losses arise from a variety of sources
and are difficult to either measure directly or to calculate, but are generally proportional to the square
of the rotor current.
Part-load performance characteristics of a motor also depend on its design. Both the n and PF fall to
very low levels at low loads. The Figures 2.2 shows the effect of load on power factor and efficiency.
It can be seen that power factor drops sharply at part loads. The Figure 2.3 shows the effect of speed
on power factor.
Field Tests for Determining Efficiency
The efficiency of the motor is given by
No Load Test: The motor is run at rated voltage and frequency without any shaft load. Input power,
current, frequency and voltage are noted. The no load P.F. is quite low and hence low PF watt meters
are required. From the input power, stator I2Rlosses under no load are subtracted to give
the sum of Friction and Windage (F&W) and core losses. To separate core and F & W losses, test is
repeated at variable voltages. It is useful to plot no-load input kW versus Voltage; the intercept is
Friction & Windage kW loss component.
F&W and core losses = No load power (Watts) — (No load current)’ x Stator resistance
Stator and Rotor PR Losses: The stator winding resistance is directly measured by a bridge or volt amp method. The resistance must be corrected to the operating temperature. For modern motors, the operating temperature is likely to be in the range of 100°C to 120°C and necessary correction should be made. Correction to 75°C may be inaccurate. The correction factor is given as follows:
The rotor resistance can be determined from locked rotor test, but rotor I?R losses are measured from
measurement of rotor slip.
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer. Slip also
must be corrected to operating temperature.
Stray Load Losses:
These losses are difficult to measure with any accuracy. IEEE Standard 112 gives a complicated method,
which is rarely used on shop floor. IS and IEC standards take a fixed value as 0.5 % of input. The actual
value of stray losses is likely to be more. IEEE — 112 specifies values from 0.9 % to 1.8 % (see Table 2.1.)
Pointers for Users:
Pointers for Users:
It must be clear that accurate determination of efficiency is very difficult. The same motor tested by
different methods and by same methods by different manufacturers can give a difference of 2 %. In
view of this, for selecting high efficiency motors, the following can be done:
a. |When purchasing large number of small motors or a large motor, ask for a detailed test
certificate. If possible, try to remain present during the tests; this will add cost.
b. See that efficiency values are specified without any tolerance
c. Check the actual input current and kW, if replacement is done
d. For new motors, keep a record of no load input power and current
e. Use values of efficiency for comparison and for confirming; rely on measured inputs for all
calculations.
a. Measure stator resistance and correct to operating temperature. From rated current value,
I’R losses are calculated.
b. From rated speed and output, rotor I°R losses are calculated
c. From no load test, core and F & W losses are determined for stray loss
The method is illustrated by the following example:
Motor Specifications
Rated power = 34 kW/45
HP
Voltage = 415
Volt
Current = 57 Amps
Speed = 1475 rpm
Insulation class = F
Frame = LD 200 L
Connection = Delta
No load test Data
Voltage, V = 415 Volts
Current, I = 16.1 Amps
Frequency, F = 50 Hz
Stator phase resistance at 30°C = 0.264 Ohms
No load power, P = 1063.74 Watts
a.Calculate iron plus friction and windage loss
b. Calculate stator resistance at 120°C
d. Calculate full load slip(s) and rotor input assuming rotor losses are slip times rotor input.
e. Determine the motor input assuming that stray losses are 0.5 % of the motor rated power
f. Calculate motor full load efficiency and full load power factor
Stray Load-Losses
Voltage unbalance is probably the leading power factor problem that results in motor over heating and
premature motor failure.
Rewinding Effects on Energy Efficiency
Comments:
a.The measurement of stray load losses is very difficult and not practical even on test beds.
b. The actual value of stray loss of motors up to 200 HP is likely to be 1 % to 3 % compared to
0.5 % assumed by standards.
c. The value of full load slip taken from the nameplate data is not accurate. Actual measurement
under full load conditions will give better results.
d. The friction and windage losses really are part of the shaft output; however, in the above
calculation, it is not added to the rated shaft output, before calculating the rotor input power.
The error however is minor.
e. When a motor is rewound, there is a fair chance that the resistance per phase would increase
due to winding material quality and the losses would be higher. It would be interesting to
assess the effect of a nominal 10 % increase in resistance per phase.
Motor Selection
The primary technical consideration defining the motor choice for any particular application is the
torque required by the load, especially the relationship between the maximum torque generated by the
motor (break-down torque) and the torque requirements for start-up (locked rotor torque) and during
acceleration periods.
The duty / load cycle determines the thermal loading on the motor. One consideration with totally
enclosed fan cooled (TEFC) motors is that the cooling may be insufficient when the motor is operated
at speeds below its rated value.
Ambient operating conditions affect motor choice; special motor designs are available for corrosive
or dusty atmospheres, high temperatures, restricted physical space, etc.
An estimate of the switching frequency (usually dictated by the process), whether automatic or manually
controlled, can help in selecting the appropriate motor for the duty cycle.
The demand a motor will place on the balance of the plant electrical system is another consideration
- if the load variations are large, for example as a result of frequent starts and stops of large components
like compressors, the resulting large voltage drops could be detrimental to other equipment.
Reliability is of prime importance - in many cases, however, designers and process engineers seeking
reliability will grossly oversize equipment, leading to sub-optimal energy performance. Good
knowledge of process parameters and a better understanding of the plant power system can aid in
reducing over sizing with no loss of reliability.
Inventory is another consideration - Many large industries use standard equipment, which can be easily
serviced or replaced, thereby reducing the stock of spare parts that must be maintained and minimizing
shut-down time. This practice affects the choice of motors that might provide better energy performance
in specific applications. Shorter lead times for securing individual motors from suppliers would help
reduce the need for this practice.
Price is another issue - Many users are first-cost sensitive, leading to the purchase of less expensive
motors that may be more costly on a lifecycle basis because of lower efficiency. For example, energy
efficient motors or other specially designed motors typically save within a few years an amount of
money equal to several times the incremental cost for an energy efficient motor, over a standardefficiency motor. Few of salient selection issues are given below:
Price is another issue - Many users are first-cost sensitive, leading to the purchase of less expensive
motors that may be more costly on a lifecycle basis because of lower efficiency. For example, energy
efficient motors or other specially designed motors typically save within a few years an amount of
money equal to several times the incremental cost for an energy efficient motor, over a standard efficiency motor. Few of salient selection issues are given below:
1.In the selection process, the power drawn at 75 % of loading can be a meaningful indicator
of energy efficiency.
2.Reactive power drawn (kVAr) by the motor.
Indian Standard 325 for standard motors allows 15 % tolerance on efficiency for motors upto
50 kW rating and 10 % for motors over 50 kW rating.
3.The Indian Standard IS 8789 addresses technical performance of Standard Motors while IS
12615 addresses the efficiency criteria of High Efficiency Motors. Both follow IEC 34-2
test methodology wherein, stray losses are assumed as 0.5 % of input power. By the IEC
test method, the losses are understated and if one goes by IEEE test methodology, the motor
efficiency values would be further lowered.
4.It would be prudent for buyers to procure motors based on test certificates rather than labeled
values. 5.The energy savings by motor replacement can be worked out by the simple relation :
6.The cost benefits can be worked out on the basis of premium required for high efficiency vs.
worth of annual savings.
Energy Efficient Motors
Energy-efficient motors (EEM), are the ones in
which, design improvements are incorporated
specifically to increase operating efficiency over
motors of standard design (see figure 2.4). Design
improvements focus on reducing intrinsic motor
losses. Improvements include the use of lower-loss
silicon steel, a longer core (to increase active
material), thicker wires (to reduce resistance),
thinner laminations, smaller air gap between stator
and rotor, copper instead of aluminum bars in the rotor, superior bearings and a smaller fan, etc. Energy-efficient motors now available in India operate with efficiencies that are typically 3 to 4 percentage points higher than standard motors. In
keeping with the stipulations of the BIS, energy-efficient motors are designed to operate without loss
in efficiency at loads between 75 % and 100 % of rated capacity. This may result in major benefits in
varying load applications. The power factor is about the same or may be higher than for standard
motors. Furthermore, energy-efficient motors have lower operating temperatures and noise levels,
greater ability to accelerate higher-inertia loads, and are less affected by supply voltage fluctuations.
Minimising Watts Loss in Motors
Improvements in motor efficiency can be achieved without compromising motor performance - at
higher cost - within the limits of existing design and manufacturing technology.
From the Table 2.2, it can be seen that any improvement in motor efficiency must result from reducing
the Watts losses. In terms of the existing state of electric motor technology, a reduction in watts losses
can be achieved in various ways.
Stator and Rotor I2R Losses
These losses are major losses and typically account for 55% to 60% of the total losses. ?R losses are
heating losses resulting from current passing through stator and rotor conductors. I’?R losses are the
function of a conductor resistance, the square of current. Resistance of conductor is a function of
conductor material, length and cross sectional area. The suitable selection of copper conductor size
will reduce the resistance. Reducing the motor current is most readily accomplished by decreasing the
magnetizing component of current. This involves lowering the operating flux density and possible
shortening of air gap. Rotor I’R losses are a function of the rotor conductors (usually aluminium) and
the rotor slip. Utilisation of copper conductors will reduce the winding resistance. Motor operation
closer to synchronous speed will also reduce rotor I’R losses.
Core Losses
Core losses are those found in the stator-rotor magnetic steel and are due to hysterisis effect and eddy
current effect during 50 Hz magnetization of the core material. These losses are independent of load
and account for 20 — 25 % of the total losses.
The hysteresis losses which are a function of flux density, are be reduced by utilizing low-loss grade
of silicon steel laminations. The reduction of flux density is achieved by suitable increase in the core length of stator and rotor. Eddy current losses are generated by circulating current within the core steel
laminations. These are reduced by using thinner laminations.
Friction and Windage Losses
Friction and windage losses results from bearing friction, windage and circulating air through the
motor and account for 8 — 12 % of total losses. These losses are independent of load. The reduction
in heat generated by stator and rotor losses permits the use of smaller fan. The windage losses also
reduce with the diameter of fan leading to reduction in windage losses.
These losses vary according to square of the load current and are caused by leakage flux induced by
load currents in the laminations and account for 4 to 5 % of total losses. These losses are reduced by
careful selection of slot numbers, tooth/slot geometry and air gap.
Energy efficient motors cover a wide range of ratings and the full load efficiencies are higher by
3 to 7 %. The mounting dimensions are also maintained as per IS1231 to enable easy replacement.
As aresult of the modifications to improve performance, the costs of energy-efficient motors are higher
than those of standard motors. The higher cost will often be paid back rapidly in saved operating costs,
particularly in new applications or end-of-life motor replacements. In cases where existing motors
have not reached the end of their useful life, the economics will be less clearly positive.
Because the favourable economics of energy-efficient motors are based on savings in operating costs,
there may be certain cases which are generally economically ill-suited to energy-efficient motors.
These include highly intermittent duty or special torque applications such as hoists and cranes, traction
drives, punch presses, machine tools, and centrifuges. In addition, energy, efficient designs of multispeed motors are generally not available. Furthermore, energy-efficient motors are not yet available
for many special applications, e.g. for flame-proof operation in oil-field or fire pumps or for very low
speed applications (below 750 rpm). Also, most energy-efficient motors produced today are designed
only for continuous duty cycle operation.
Given the tendency of over sizing on the one hand and ground realities like; voltage, frequency
variations, efficacy of rewinding in case of a burnout, on the other hand, benefits of EEM’s can be
achieved only by careful selection, implementation, operation and maintenance efforts of energy
managers.
Technical aspects of Energy Efficient Motors
Energy-efficient motors last longer, and may require less maintenance. At lower temperatures, bearing
grease lasts longer; required time between re-greasing increases. Lower temperatures translate to long
lasting insulation. Generally, motor life doubles for each 10°C reduction in operating temperature.
Select energy-efficient motors with a 1.15 service factor, and design for operation at 85% of the rated
motor load.
Electrical power problems, especially poor incoming power quality can affect the operation of
energy-efficient motors.
Speed control is crucial in some applications. In polyphase induction motors, slip is a measure of
motor winding losses. Lower the slip, higher the efficiency. Less slippage in energy efficient motors
results in speeds about 1% faster than in standard counterparts.
Starting torque for efficient motors may be lower than for standard motors. Facility managers should
be careful when applying efficient motors to high torque applications.
Factors Affecting Energy Efficiency & Minimising Motor Losses in Operation
Power Supply Quality
Motor performance is affected considerably by the quality of input power that is the actual volts and
frequency available at motor terminals vis-a-vis rated values as well as voltage and frequency variations
and voltage unbalance across the three phases. Motors in India must comply with standards set by the
Bureau of Indian Standards (BIS) for tolerance to variations in input power quality. The BIS standards
specify that a motor should be capable of delivering its rated output with a voltage variation of +/- 6
% and frequency variation of +/- 3 %. Fluctuations much larger than these are quite common in utilitysupplied electricity in India. Voltage fluctuations can have detrimental impacts on motor performance.
The general effects of voltage and frequency variation on motor performance are presented in
Table 2.3:
Voltage unbalance, the condition where the voltages in the three phases are not equal, can be still more
detrimental to motor performance and motor life. Unbalance typically occurs as a result of supplying
single-phase loads disproportionately from one of the phases. It can also result from the use of different
sizes of cables in the distribution system. An example of the effect of voltage unbalance on motor
performance is shown in Table 2.4.
The NEMA (National Electrical Manufacturers Association of USA) standard definition of voltage
unbalance is given by the following equation:
Common Causes of Voltage Unbalance
It is recommended that the voltage unbalance at the motor terminals not exceed 1% , anything above
this will lead to derating of the motor. The common causes of voltage unbalance are
Some of the more common causes of unbalanced voltages are:
o Unbalanced incoming utility supply
o Unequal transformer tap settings
o Large single phase distribution transformer on the system
o Open phase on the primary of a 3 phase transformer on the distribution system
o Faults or grounds in the power transformer
o Open delta connected transformer banks
o A blown fuse on a 3 phase bank of power factor improvement capacitors
o Unequal impedance in conductors of power supply wiring
o
Unbalanced distribution of single phase loads such as lighting
o Heavy reactive single phase loads such as welders
Voltage unbalance causes extremely high current imbalance. The magnitude of current imbalance may
be 6 to 10 times as large as the voltage imbalance. A motor will run hotter when operating on a power
supply with voltage unbalance. The additional temperature rise is estimated with the following equation
For example, if the voltage unbalance is 2% for a motor operating at 100 °C, the additional temperature
rise will be 8 °C. The winding insulation life is reduced by one half for each 10 °C increase in operating
temperature.
Motor Loading
Motor Loading
Measuring Load
% Loading of the motor can be estimated by the following relation:
Large industries have a massive population of LT motors. Load survey of LT motors can be taken-up
methodically to identify improvement options as illustrated in following case study.
i) Sampling Criteria
i) Sampling Criteria
Towards the objective of selecting representative LT motor drives among the motor population, for
analysis, the criteria considered are:
¢ Utilization factor i.e., hours of operation with preference given to continuously operated drive motors.
¢ Utilization factor i.e., hours of operation with preference given to continuously operated drive motors.
¢ Sample representative basis, where one drive motor analysis can be reasoned as representative
for the population. Ex : Cooling Tower Fans, Air Washer Units, etc.
¢ Conservation potential basis, where drive motors with inefficient capacity controls on the
machine side, fluctuating load drive systems, etc., are looked into.
ii) Measurements
Studies on selected LT motors involve measurement of electrical load parameters namely volts, amperes,
power factor, kW drawn.
Observations on machine side parameters such as speed, load, pressure, temperature, etc., (as relevant)
are also taken. Availability of online instruments for routine measurements, availability of tail-end
capacitors for PF correction, energy meters for monitoring is also looked into for each case.
iii) Analysis
Analysis of observations on representative LT motors and connected drives is carried out towards
following outputs:
¢ Motor load on kW basis and estimated energy consumption.
¢ Scope for improving monitoring systems to enable sustenance of a regular in-house Energy
Audit function.
¢ Scope areas for energy conservation with related cost benefits and source information.
The observations are to indicate:
% loading on kW, % voltage unbalance if any, voltage, current, frequency, power factor, machine side
conditions like load / unload condition, pressure, flow, temperature, damper / throttle operation, whether
it is arewound motor, idle operations, metering provisions, etc.
The findings / recommendations may include:
¢ Identified motors with less than 50 % loading, 50 — 75 % loading, 75 — 100 % loading, over 100
% loading.
¢ Identified motors with low voltage / power factor / voltage imbalance for needed improvement
measures.
¢ Identified motors with machine side losses / inefficiencies like idle operations, throttling /
damper operations for avenues like automatic controls / interlocks, variable speed drives, etc.
Motor load survey is aimed not only as a measure to identify motor efficiency areas but equally
importantly, as a means to check combined efficiency of the motor, driven machine and controller if any. The margins in motor efficiency may be less than 10 % of consumption often, but the load survey
would help to bring out savings in driven machines / systems, which can give 30 — 40 % energy savings.
Reducing Under-
loading
Probably the most common practice contributing to sub-optimal motor efficiency is that of underloading. Under-loading results in lower efficiency and power factor, and higher-than-necessary first
cost for the motor and related control equipment. Under-loading is common for several reasons.
Original equipment manufacturers tend to use a large safety factor in motors they select. Under-loading
of the motor may also occur from under-utilisation of the equipment. For example, machine tool
equipment manufacturers provide for a motor rated for the full capacity load of the equipment ex.
depth of cut in a lathe machine. The user may need this full capacity rarely, resulting in under-loaded
operation most of the time. Another common reason for under-loading is selection of a larger motor
to enable the output to be maintained at the desired level even when input voltages are abnormally
low. Finally, under-loading also results from selecting a large motor for an application requiring high
starting torque where a special motor, designed for high torque, would have been suitable.
A careful evaluation of the load would determine the capacity of the motor that should be selected.
Another aspect to consider is the incremental gain in efficiency achievable by changing the motor.
Larger motors have inherently higher rated efficiencies than smaller motors. Therefore, the replacement
of motors operating at 60 — 70 % of capacity or higher is generally not recommended. However, there
are no rigid rules governing motor selection; the savings potential needs to be evaluated on a case-tocase basis. When downsizing, it may be preferable to select an energy-efficient motor, the efficiency
of which may be higher than that of a standard motor of higher capacity.
Improving the Motor Loading by Operating in Star Mode
For motors, which consistently operate at loads below 40 % of rated capacity, an inexpensive and
effective measure might be to operate in star mode. A change from the standard delta operation to
permanent star operation involves re-configuring the wiring at terminal box and resetting of the over
current relay.
Operating in the star mode leads to a voltage reduction by a factor of ‘V3’. Motor is electrically
downsized by 1/3" in star mode operation, but performance characteristics as a function of load remain
unchanged. For example if a motor is rated for 15 kW in delta mode, its derated capacity is 5kW in
star mode. Thus, full-load operation in star mode gives higher efficiency and power factor than partial
load operation in the delta mode. However, motor operation in the star mode is possible only for
applications where the torque-to-speed requirement is lower at reduced load.
As speed of the motor reduces in star mode this option may be avoided in case the motor is connected
to a production facility whose output is related to the motor speed. Further in star mode the motor
loading should not be allowed to cross derated capacity. For example in above case of 15 kW delta
connected electric motor, should not be loaded above 5 kW when delta to star switchover takes place.
For applications with high initial torque and low running torque needs, automatic Star-Del-Star
converters are also available, which help in load following de-rating of electric motors after initial
Start-up.
Sizing to Variable Load
Industrial motors frequently operate under varying load conditions due to process requirements. A
common practice in cases where such variable-loads are found is to select a motor based on the highest
anticipated load. In many instances, an alternative approach is typically less costly, more efficient,
and provides equally satisfactory operation. With this approach, the optimum rating for the motor is
selected on the basis of the load duration curve for the particular application. Thus, rather than selecting
a motor of high rating that would operate at full capacity for only a short period, a motor would be
selected with a rating slightly lower than the peak anticipated load and would operate at overload for
a short period of time. Since operating within the thermal capacity of the motor insulation is of greatest
concern in a motor operating at higher than its rated load, the motor rating is selected as that which
would result in the same temperature rise under continuous full-load operation as the weighted average
temperature rise over the actual operating cycle. Under extreme load changes, e.g. frequent starts /
stops, or high inertial loads, this method of calculating the motor rating is unsuitable since it would
underestimate the heating that would occur.
Where loads vary substantially with time, in addition to proper motor sizing, the control strategy
employed can have a significant impact on motor electricity use. Traditionally, mechanical means
(e.g. throttle valves in piping systems) have been used when lower output is required. More efficient
speed control mechanisms include multi-speed motors, eddy-current couplings, fluid couplings, and
solid-state electronic variable speed drives.
Power Factor
Correction
As noted earlier, induction motors are characterized by power factors less than unity, leading to lower
overall efficiency (and higher overall operating cost) associated with a plant’s electrical system.
Capacitors connected in parallel (shunted) with the motor are typically used to improve the power
factor. The impacts of PF correction include reduced kVA demand (and hence reduced utility demand
charges), reduced I’R losses in cables upstream of the capacitor (and hence reduced energy charges),
reduced voltage drop in the cables (leading to improved voltage regulation), and an increase in the
overall efficiency of the plant electrical system.
It should be noted that PF capacitor improves power factor from the point of installation back to the
generating side. It means that, if a PF capacitor is installed at the starter terminals of the motor, it won’t
improve the operating PF of the motor, but the PF from starter terminals to the power generating side
will improve, i.e., the benefits of PF would be only on upstream side.
The size of capacitor required for a particular motor depends upon the no-load reactive kVA (kVAR)
drawn by the motor, which can be determined only from no-load testing of the motor. In general, the
capacitor is then selected to not exceed 90 % of the no-load kVAR of the motor. (Higher capacitors
could result in over-voltages and motor burn-outs). Alternatively, typical power factors of standard
motors can provide the basis for conservative estimates of capacitor ratings to use for different size
motors. The capacitor rating for power connection by direct connection to induction motors is shown
in Table 2.5.
From the above table, it may be noted that required capacitive kVAr increases with decrease in speed
of the motor, as the magnetizing current requirement of a low speed motor is more in comparison to
the high speed motor for the same HP of the motor. Since a reductions in line current, and associated
energy efficiency gains, are reflected backwards from the point of application of the capacitor, the
maximum improvement in overall system efficiency is achieved when the capacitor is connected across
the motor terminals, as compared to somewhere further upstream in the plant’s electrical system.
However, economies of scale associated with the cost of capacitors and the labor required to install
them will place an economic limit on the lowest desirable capacitor size.
Maintenance
Inadequate maintenance of motors can significantly increase losses and lead to unreliable
operation. For example, improper lubrication can cause increased friction in both the
motor and associated drive transmission equipment. Resistance losses in the motor, which rise with
temperature, would increase. Providing adequate ventilation and keeping motor cooling ducts clean
can help dissipate heat to reduce excessive losses. The life of the insulation in the motor would also
be longer : for every 10°C increase in motor operating temperature over the recommended peak, the
time before rewinding would be needed is estimated to be halved.
A checklist of good maintenance practices to help insure proper motor operation would include:
a). Inspecting motors regularly for wear in bearings and housings (to reduce frictional losses)
and for dirt/dust in motor ventilating ducts (to ensure proper heat dissipation).
b).Checking load conditions to ensure that the motor is not over or under loaded. A change in
motor load from the last test indicates a change in the driven load, the cause of which should
be understood.
c)Lubricating appropriately. Manufacturers generally give recommendations for how and
when to lubricate their motors. Inadequate lubrication can cause problems, as noted above.
Over-lubrication can also create problems, e.g. excess oil or grease from the motor bearings
can enter the motor and saturate the motor insulation, causing premature failure or creating
a fire risk.
d)Checking periodically for proper alignment of the motor and the driven equipment. Improper
alignment can cause shafts and bearings to wear quickly, resulting in damage to both the
motor and the driven equipment.
e)Ensuring that supply wiring and terminal box are properly sized and installed. Inspect
regularly the connections at the motor and starter to be sure that they are clean and tight.
Age
Most motor cores in India are manufactured from silicon steel or de-carbonized cold-rolled steel, the
electrical properties of which do not change measurably with age. However, poor maintenance
(inadequate lubrication of bearings, insufficient cleaning of air cooling passages, etc.) can cause a
deterioration in motor efficiency over time. Ambient conditions can also have a detrimental effect on
motor performance. For example, excessively high temperatures, high dust loading, corrosive
atmosphere, and humidity can impair insulation properties; mechanical stresses due to load cycling
can lead to misalignment. However, with adequate care, motor performance can be maintained.
It is common practice in industry to rewind burnt-out motors. The population of rewound motors in
some industries exceeds 50 % of the total population. Careful rewinding can sometimes maintain
motor efficiency at previous levels, but in most cases, losses in efficiency result. Rewinding can affect
a number of factors that contribute to deteriorated motor efficiency: winding and slot design, winding
material, insulation performance, and operating temperature. For example, a common problem occurs
when heat is applied to strip old windings: the insulation between laminations can be damaged, thereby
increasing eddy current losses. A change in the air gap may affect power factor and output torque.
However, if proper measures are taken, motor efficiency can be maintained, and in some cases increased,
after rewinding. Efficiency can be improved by changing the winding design, though the power factor
could be affected in the process. Using wires of greater cross section, slot size permitting, would reduce
stator losses thereby increasing efficiency. However, it is generally recommended that the original
design of the motor be preserved during the rewind, unless there are specific, load-related reasons for
redesign.
The impact of rewinding on motor efficiency and power factor can be easily assessed if the no-load
losses of a motor are known before and after rewinding. Maintaining documentation of no-load losses
and no-load speed from the time of purchase of each motor can facilitate assessing this impact. For
example, comparison of no load current and stator resistance per phase of a rewound motor with the original no-load current and stator resistance at the same voltage can be one of the indicators to assess
the efficacy of rewinding.
Performance Evaluation of Rewound Motors
Ideally, a comparison should be made of the efficiency before and after a rewinding. A relatively simple
procedure for evaluating rewind quality is to keep a log of no-load input current for each motor in the
population. This figure increases with poor quality rewinds. A review of the rewind shop’s procedure
should also provide some indication of the quality of work. When rewinding a motor, if smaller diameter
wire is used, the resistance and the I’R losses will increase.
Ideally, a comparison should be made of the efficiency before and after a rewinding. A relatively simple
procedure for evaluating rewind quality is to keep a log of no-load input current for each motor in the
population. This figure increases with poor quality rewinds. A review of the rewind shop’s procedure
should also provide some indication of the quality of work. When rewinding a motor, if smaller diameter
wire is used, the resistance and the I’R losses will increase.
The monitoring format for rewound motor is given Table 2.6 below:
Speed Control of Motors
Traditionally, DC motors have been employed when variable speed capability was desired. By
controlling the armature (rotor) voltage and field current of a separately excited DC motor, a wide
range of output speeds can be obtained. DC motors are available in a wide range of sizes, but their use
is generally restricted to a few low speed, low-to-medium power applications like machine tools and
rolling mills because of problems with mechanical commutation at large sizes. Also, they are restricted
for use only in clean, non-hazardous areas because of the risk of sparking at the brushes. DC motors
are also expensive relative to AC motors.
Because of the limitations of DC systems, AC motors are increasingly the focus for variable speed
applications. Both AC synchronous and induction motors are suitable for variable speed control.
Induction motors are generally more popular, however, because of their ruggedness and lower
maintenance requirements. AC induction motors are inexpensive (half or less of the cost of a DC
motor) and also provide a high power to weight ratio (about twice that of a DC motor). An induction motor is an asynchronous motor, the speed of which can be varied by changing the supply
frequency. The control strategy to be adopted in any particular case will depend on a number of factors
including investment cost, load reliability and any special control requirements. Thus, for any particular
application, a detailed review of the load characteristics, historical data on process flows, the features
required of the speed control system, the electricity tariffs and the investment costs would be a
prerequisite to the selection of a speed control system.
The characteristics of the load are particularly important. Load refers essentially to the torque output
and corresponding speed required. Loads can be broadly classified as either constant power or constant
torque. Constant torque loads are those for which the output power requirement may vary with the
speed of operation but the torque does not vary. Conveyors, rotary kilns, and constant-displacement
pumps are typical examples of constant torque loads. Variable torque loads are those for which the
torque required varies with the speed of operation. Centrifugal pumps and fans are typical examples
of variable torque loads (torque varies as the square of the speed). Constant power loads are those for
which the torque requirements typically change inversely with speed. Machine tools are a typical
example of a constant power load.
The largest potential for electricity savings with variable speed drives is generally in variable torque
applications, for example centrifugal pumps and fans, where the power requirement changes as the
cube of speed. Constant torque loads are also suitable for VSD application.
Motor Speed Control Systems
Multi-speed motors
Motors can be wound such that two speeds, in the ratio of 2:1, can be obtained. Motors can also be wound with two separate windings, each giving 2 operating speeds, for a total of four speeds. Multispeed motors can be designed for applications involving constant torque, variable torque, or for constant output power. Multi-speed motors are suitable for applications, which require limited speed control (two or four fixed speeds instead of continuously variable speed), in which cases they tend to be very economical. They have lower efficiency than single-speed motors
Motors can be wound such that two speeds, in the ratio of 2:1, can be obtained. Motors can also be wound with two separate windings, each giving 2 operating speeds, for a total of four speeds. Multispeed motors can be designed for applications involving constant torque, variable torque, or for constant output power. Multi-speed motors are suitable for applications, which require limited speed control (two or four fixed speeds instead of continuously variable speed), in which cases they tend to be very economical. They have lower efficiency than single-speed motors
Direct Current Drives (DC)
The DC drive technology is the oldest form of electrical speed control. The drive system consists of
a DC motor and a controller. The motor is constructed with armature and field windings. Both of
these windings require a DC excitation for motor operation. Usually the field winding is excited with
a constant level voltage from the controller.
Then, applying a DC voltage from the controller to the armature of the motor will operate the motor. The armature connections are made through a brush and commutator assembly. The speed of the motor is directly proportional to the applied voltage.
Then, applying a DC voltage from the controller to the armature of the motor will operate the motor. The armature connections are made through a brush and commutator assembly. The speed of the motor is directly proportional to the applied voltage.
The controller is a phase controlled bridge rectifier with logic circuits to control the DC voltage
delivered to the motor armature. Speed control is achieved by regulating the armature voltage to the
motor. Often a tachogenerator is included to achieve good speed regulation. The tachogenerator would
be mounted on the motor and produces a speed feedback signal that is used within the controller.
Wound Rotor AC Motor Drives (Slip Ring Induction Motors)
Wound rotor motor drives use a specially constructed motor to accomplish speed control. The motor
rotor is constructed with windings which are brought out of the motor through slip rings on the motor
shaft. These windings are connected to a controller which places variable resistors in series with the
windings. The torque performance of the motor can be controlled using these variable resistors. Wound
rotor motors are most common in the range of 300 HP and above.
Slip Power Recovery Systems
Slip power recovery is a more efficient alternative speed control mechanism for use with slip-ring
motors. In essence, a slip power recovery system varies the rotor voltage to control speed, but instead
of dissipating power through resistors, the excess power is collected from the slip rings and returned
as mechanical power to the shaft or as electrical power back to the supply line. Because of the relatively
sophisticated equipment needed, slip power recovery tends to be economical only in relatively high
power applications and where the motor speed range is 1:5 or less.
Application of Variable Speed Drives (VSD)
Although there are many methods of varying the speeds of the driven equipment such as hydraulic
coupling, gear box, variable pulley etc., the most possible method is one of varying the motor speed
itself by varying the frequency and voltage by a variable frequency drive.
Concept of Variable Frequency Drive
The speed of an induction motor is proportional to the frequency of the AC voltage applied to it, as
well as the number of poles in the motor stator. This is expressed by the equation:
Therefore, if the frequency applied to the motor is changed, the motor speed changes in direct proportion
to the frequency change. The control of frequency applied to the motor is the job given to the VSD.
The VSD’s basic principle of operation is to convert the electrical system frequency and voltage to
the frequency and voltage required to drive a motor at a speed other than its rated speed. The two most
basic functions of a VSD are to provide power conversion from one frequency to another, and to enable
control of the output frequency.
Earlier motors tended to be over designed to drive a specific load over its entire range. This resulted
ina highly inefficient driving system, as a significant part of the input power was not doing any useful
work. Most of the time, the generated motor torque was more than the required load torque.
In many applications, the input power is a function of the speed like fan, blower, pump and so on. In
these types of loads, the torque is proportional to the square of the speed and the power is proportional
to the cube of speed. Variable speed, depending upon the load requirement, provides significant energy
saving. A reduction of 20% in the operating speed of the motor from its rated speed will result in an
almost 50% reduction in the input power to the motor. This is not possible in a system where the motor
is directly connected to the supply line. In many flow control applications, a mechanical throttling
device is used to limit the flow. Although this is an effective means of control, it wastes energy because
of the high losses and reduces the life of the motor valve due to generated heat.
Principles of VFD’s
The VFD is a system made up of active/passive
power electronics devices (IGBT, MOSFET, etc.), a high speed central controlling unit and optional sensing devices, depending upon the application requirement. A typical modern-age intelligent VFD for the three phase induction motor is shown in Figure 2.5.
The basic function of the VFD is to act as a variable frequency generator in order to vary
speed of the motor as per the user setting. The rectifier and the filter convert the AC input to
DC with negligible ripple. The inverter, under the control of the microcontroller, synthesizes the DC
into three-phase variable voltage, variable frequency AC.
The base speed of the motor is proportional to supply frequency and is inversely proportional to the
number of stator poles. The number of poles cannot be changed once the motor is constructed. So, by
changing the supply frequency, the motor speed can be changed. But when the supply frequency is
reduced, the equivalent impedance of electric circuit reduces. This results in higher current drawn by the
motor and a higher flux. If the supply voltage is not reduced, the magnetic field may reach the saturation
level. Therefore, in order to keep the magnetic flux within working range, both the supply voltage and
the frequency are changed in a constant ratio. Since the torque produced by the motor is proportional to
the magnetic field in the air gap, the torque remains more or less constant throughout the operating range.
As seen in Figure 2.6, the voltage and the frequency are varied at a constant ratio up to the base speed.
The flux and the torque remain almost constant up to the base speed. Beyond the base speed, the supply
voltage cannot be increased. Increasing the frequency beyond the base speed results in the field
weakening and the torque reduces. Above the base speed, the torque governing factors become more
nonlinear as the friction and windage losses increase significantly. Due to this, the torque curve becomes
nonlinear. Based on the motor type, the field weakening can go up to twice the base speed. This control
is the most popular in industries and is popularly known as the constant V/f control.
By selecting the proper V/f ratio for a motor, the starting current can be kept well under control. This
avoids any sag in the supply line, as well as heating of the motor. The VFD also provides overcurrent
protection. This feature is very useful while controlling the motor with higher inertia. Since almost
constant rated torque is available over the entire operating range, the speed range of the motor becomes
wider. User can set the speed as per the load requirement, thereby achieving higher energy efficiency
(especially with the load where power is proportional to the cube speed). Continuous operation over
almost the entire range is smooth, except at very low speed. This restriction comes mainly due to the
inherent losses in the motor, like frictional, windage, iron, etc. These losses are almost constant over
the entire speed. Therefore, to start the motor, sufficient power must be supplied to overcome these
losses and the minimum torque has to be developed to overcome the load inertia.
A single VFD has the capability to control multiple motors. The VFD is adaptable to almost any
operating condition.
VFD Selection
The size of the VFD depends mainly on driven load type and characteristics. This will determine the
drive capacity in terms of full load current (FLC) and power delivered (kW).
Driven Load Types and Characteristics
Mechanical load, which is the load on the motor shaft, can be of two types- Constant Torque (CT) or
Variable Torque (VT). There is a basic difference between the two loads with respect to load torque
variation at different speeds.
A CT load implies that the load torque seen at motor shaft is independent of motor speed.
This means that the load torque remains approximately the same at all speeds. Examples of CT loads
include material handling conveyers, reciprocating & screw compressors and certain types of blowers
such as roots blower.
A VT load implies that the load torque seen at the motor shaft is dependent upon the motor speed.
Examples of VT loads include centrifugal fans & pumps and centrifugal compressors.
The graphs (Figures 2.7 & 2.8) below describe the torque requirements at various speeds.
Other methods of speed control of motors
In addition to DC drives, VFD and slip ring motors there are other methods used in industries to control
the speed of the motors. Some of the common methods used in industries are discussed below:
Eddy Current Drives
This method employs an eddy-current clutch to vary the output speed. The clutch consists of a primary
member coupled to the shaft of the motor and a freely revolving secondary member coupled to the load shaft. The secondary member is separately excited using
a DC field winding. The motor starts with the load at rest and a DC excitation is provided to the secondary member, which induces eddy-currents in the primary member. The interaction of the fluxes produced by the two currents gives rise to a torque at the load shaft. By varying the DC excitation the output speed can be varied to match the load requirements. The major disadvantage of this system is relatively poor efficiency particularly at low speeds. (See Figure 2.9)
Fluid Coupling
Fluid coupling is one way of applying varying speeds to the driven equipment, without changing the
speed of the motor.
Fluid couplings (see Figure 2.10) work on the hydrodynamic
principle. Inside every fluid coupling are two basic elements
— the impeller and the runner and together they constitute
the working circuit. One can imagine the impeller as a
centrifugal pump and the runner as a turbine. The impeller
and the rotor are bowl shaped and have large number of
radial vanes. They are suitably enclosed in a casing, facing
each other with an air gap. The impeller is connected to the
prime mover while the rotor has a shaft bolted to it. This
shaft is further connected to the driven equipment through
a suitable arrangement.
hin mineral oil of low viscosity and good-lubricating
qualities is filled in the fluid coupling from the filling plug
provided on its body. A fusible plug is provided on the fluid
coupling which blows off and drains out oil from the
coupling in case of sustained overloading. Operating Principle
There is no mechanical inter-connection between the impeller and the rotor and the power is transmitted
by virtue of the fluid filled in the coupling. When the impeller is rotated by the prime mover, the fluid
flows out radially and then axially under the action of centrifugal force. It then crosses the air gap to
the runner and is directed towards the bowl axis and back to the impeller. To enable the fluid to flow
from impeller to rotor it is essential that there is difference in head between the two and thus it is
essential that there is difference in RPM known as slip between the two. Slip is an important and
inherent characteristic of a fluid coupling resulting in several desired advantages. As the slip increases,
more and more fluid can be transferred. However when the rotor is at a stand still, maximum fluid is
transmitted from impeller to rotor and maximum torque is transmitted from the coupling. This maximum
torque is the limiting torque. The fluid coupling also acts as a torque limiter.
Characteristics
Fluid coupling has a centrifugal characteristic during starting thus enabling no-load start up of prime
mover, which is of great importance. The slipping characteristic of fluid coupling provides a wide
range of choice of power transmission characteristics. By varying the quantity of oil filled in the fluid
coupling, the normal torque transmitting capacity can be varied. The maximum torque or limiting
torque of the fluid coupling can also be set to a pre-determined safe value by adjusting the oil filling.
The fluid coupling has the same characteristics in both directions of rotation.
Soft Starter
When starting, AC Induction motor develops more torque than is required a
at full speed. This stress is transferred to the mechanical transmission system
resulting in excessive wear and premature failure of chains, belts, gears,
mechanical seals, etc. Additionally, rapid acceleration also has a massive
impact on electricity supply charges with high inrush currents drawing
+600% of the normal run current.
The use of Star Delta only provides a partial solution to the problem. Should the motor slow down during the transition period, the high peaks can be
repeated and can even exceed direct on line current.
Soft starter (see Figure 2.11) provides a reliable and economical solution to these problems by delivering
a controlled release of power to the motor, thereby providing smooth, stepless acceleration and
deceleration. Motor life will be extended as damage to windings and bearings is reduced.
Soft Start & Soft Stop is built into 3 phase units, providing controlled starting and stopping with a
selection of ramp times and current limit settings to suit all applications (see Figure 2.12).
Advantages of Soft Start
— Less mechanical stress
— Improved power factor.
— Lower maximum demand.
— Less mechanical maintenance
Star Labeling of Energy Efficient Induction Motors
The schedule specifies the requirements for participating in the energy labeling scheme for 3 phase
squirrel cage induction motor in 2 Pole, 4 Pole and 6 Pole for continuous duty (S1) operation, suitable
for voltage and frequency variation as per IS 12615:2011 having rated output from 0.37 to 375 kW.
In particular, this scheme specifies the following:
1. Rated output (rating) 2. Efficiency Class based on IS 12615:2011 i.e. (TE2, TE2(+), IE3, [E3(+) and IE3 (++))
3. Some of the requirements for energy label validity.
4. The performance criteria for energy labeling validity.
5. Test report format.
6. Label design and details to be incorporated on the label.
The plant operates for 7000 hours per year with the electricity cost of Rs. 6.00 per unit.
It is proposed to replace the existing motor by a 30 kW energy efficient motor with 92% efficiency.
a) Determine the rated efficiency and the loading of the existing motor.
b) Calculate the loading with energy efficient motor.
c) Ifreplacing the existing motor with energy efficient motor which costs Rs.75,000, determine
the payback period for the investment required for the energy efficient motor over the existing
motor. Consider the salvage value of the existing motor as Rs.10,000/.
-----------------------
Comments
Post a Comment